- Grundfos Ghana
- Learn
- Ecademy
- All courses
- 69 - The Grundfos Distribut...
- Test your knowledge
Question 1 of 6
Intermediate
Why must low-pressure non-return valves be installed for each cooling loop with AHU’s?
Question 2 of 6
Intermediate
What is the benefit of aligning primary side flow with secondary side flow?
Question 3 of 6
Intermediate
How does distributed pumping ensure minimum flow over each chiller?
Question 4 of 6
Intermediate
How does the MPC controller protect chillers from freezing?
Question 5 of 6
Intermediate
What is the key design element in Grundfos Distributed Pumping?
Question 6 of 6
Intermediate
With a single dedicated pump for each terminal unit, which control mode is used?
Question 6 of 6
Intermediate
Happy with your answers?
Submit your current answers and get the final test result.
Test results
Congratulations. You have passed the test and completed the 69 - The Grundfos Distributed Pumping Course
Sorry. You did not pass the 69 - The Grundfos Distributed Pumping Course test this time
Achieved badges:
How would you rate this course?
1: Why must low-pressure non-return valves be installed for each cooling loop with AHU’s?
You don’t need non-return valves – intelligent pumps make all valves redundanteed
You can find the answer here >
1: Why must low-pressure non-return valves be installed for each cooling loop with AHU’s?
To avoid backflow in case the AHU unit is out of operation
1: Why must low-pressure non-return valves be installed for each cooling loop with AHU’s?
You only need non-return valves for proportional pressure installations
You can find the answer here >
2: What is the benefit of aligning primary side flow with secondary side flow?
To ensure distributed pumps never miss water on the suction side
You can find the answer here >
2: What is the benefit of aligning primary side flow with secondary side flow?
To avoid increasing pressure in the bypass pipe
You can find the answer here >
2: What is the benefit of aligning primary side flow with secondary side flow?
To avoid or minimise the ‘low’ Delta T syndrome
3: How does distributed pumping ensure minimum flow over each chiller?
By having a differential pressure sensor installed across each chiller
3: How does distributed pumping ensure minimum flow over each chiller?
By running with maximum flow at maximum load
You can find the answer here >
3: How does distributed pumping ensure minimum flow over each chiller?
By ensuring the primary pump is larger than in a conventional system
You can find the answer here >
4: How does the MPC controller protect chillers from freezing?
By fulfilling the chiller setpoint signal
You can find the answer here >
4: How does the MPC controller protect chillers from freezing?
By ensuring minimum flow over the active chille
4: How does the MPC controller protect chillers from freezing?
By chiller temperature signal
You can find the answer here >
5: What is the key design element in Grundfos Distributed Pumping?
A new kind of intelligent valve
You can find the answer here >
5: What is the key design element in Grundfos Distributed Pumping?
The use of intelligent pumps instead of valves
5: What is the key design element in Grundfos Distributed Pumping?
Making bypass lines obsolete
You can find the answer here >
6: With a single dedicated pump for each terminal unit, which control mode is used?
Proportional pressure
You can find the answer here >
6: With a single dedicated pump for each terminal unit, which control mode is used?
Proportional pressure or constant temperature – doesn’t matter
You can find the answer here >
6: With a single dedicated pump for each terminal unit, which control mode is used?
Constant temperature